Keyence DL-PN1 User Manual Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
6
- PROFINET Communication Unit DL-PN1 User's Manual (IB) -
* "a" represents a Slot number. When Addresses were assigned in order, the Address
for Slot 1 is 16, 17, 18, or 19 to 22.
Data I/O communication device map (PROFINET I/O controller DL-PN1)
DL-PN1 (Slot 0)
Output
17+7(a-1)*
0 Reserved for system - -
1 Comparator value invalid Stores the comparator value status.
0: Normal
1: Comparator value invalid
----
2 Comparator value under range Stores the comparator value status.
0: Normal
1: Comparator value under
range “-FFFF
3 Comparator value over range Stores the comparator value status.
0: Normal
1: Comparator value over
range “FFFF
4 Reserved for system - -
5 Reserved for system - -
6 Warning
Represents the warning status of the
sensor.
"Types of error and error code"
(page 29)
0: No warning
1: Warning
7 Error status
Stores the error status of the sensor
amplifiers.
"Types of error and error code"
(page 29)
0: No error occurred.
1: Error occurred.
18+7(a-1)*
0 External input response 1
Stores the external input response
to the sensor amplifier.
0: No input
1: Input reception
1 External input response 2
Stores the external input response
to the sensor amplifier.
0: No input
1: Input reception
2 External input response 3
Stores the external input response
to the sensor amplifier.
0: No input
1: Input reception
3 External input response 4
Stores the external input response
to the sensor amplifier.
0: No input
1: Input reception
4 Reserved for system - -
5 Reserved for system - -
6 Reserved for system - -
7 Reserved for system - -
19+7(a-1)* to
22+7(a-1)*
0 to 7 Comparator value
Used when reading the comparator
value (P.V. value).
INT32
Address Bit Function name Description Value
Address Bit Function name Description Value
0
0 External input request 1
*1
Requests the external input to the
sensor amplifiers.
0: OFF
1: ON
1 External input request 2
*1
Requests the external input to the
sensor amplifiers.
0: OFF
1: ON
2 External input request 3
*1
Requests the external input to the
sensor amplifiers.
0: OFF
1: ON
3 External input request 4
*1
Requests the external input to the
sensor amplifiers.
0: OFF
1: ON
4 Reserved for system - -
5 Reserved for system - -
6 Reserved for system - -
7 Reserved for system - -