3-2 Device Maps
3-17
3
Communicating with the SK-1000 Series
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (SK-1000) -
*3 Refer to "Monitor mode 2/full mode" (page 3-20).
*4 Refer to "Error information list" (page 3-9).
*5 Refer to "Command response list" (page 3-10).
*6 Refer to "Command Parameter List" (page 3-26).
Remote register RWw (master station -> DL-CL1)
Number [n] denotes the first relay number assigned to the DL-CL1.
*1 Refer to "Changing the BANK Number of Sensor Amplifiers" (page 3-21).
*2 Refer to "Reading/Writing Settings or Status of a Sensor Amplifier" (page 3-23).
Refer to "Issuing a Motion Command to a Sensor Amplifier" (page 3-22).
*3 Refer to "Rewriting a Setting Value of a Sensor Amplifier" (page 3-23).
*4 Refer to "Command Parameter List" (page 3-26).
Operating
mode
Device no.
(HEX)
Name
Communication
method
Description Writing range
Monitor mode 1
Full mode 1
Full mode 2
RWw[n] + 00
Data category/
command
number
Used when communicating under
handshake control program.
Specifies the data category and
command number of the
parameter to be communicated.
Upper byte:
00h - FFh
Lower byte:
00: Read
01: Write
02: Motion
command
RWw[n] + 01 Data number *3
Used when communicating under
handshake control program.
Specifies the data number of the
parameter to be communicated.
0000h - FFFFh
RWw[n] + 02
to 03
(2 words)
Data to write *3
Used when communicating under
handshake control program.
Specifies the data to be written in
the parameter to be
communicated.
*4
RWw[n] + 04
Select BANK
number
*2
Used when changing BANK
number.
Specifies a new BANK number.
0: BANK 0
1: BANK 1
2: BANK 3
3: BANK 3
RWw[n] + 05
System reserved
- Unusable -
RWw[n] + 06
to 07
HI setting value
(BANK 0)
rewrite data
*4
Stores the HI setting value (BANK
0) to be written in the sensor
amplifier.
INT32 (LITTLE)
RWw[n] + 08
to 09
LO setting
value (BANK 0)
rewrite data
*4
Stores the LO setting value (BANK
0) to be written in the sensor
amplifier.
INT32 (LITTLE)