3-2 Device Maps
3-13
3
Communicating with the FD-MH series
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-MH) -
Operating
mode
Device
no. (HEX)
Name
Communication
method
Description Writing range
Monitor mode 2
Full mode 1
Full mode 2
RY[n] + 53
Current Value
Update Request
-
Used when locking data update of current
value. This may be used to obtain the current
values of multiple sensor amplifi ers at the
same timing.
The current value is locked while the update
request is held.
The update lock state can be checked by the
current value update lock state (RX[n] + 53).
0: Do not lock
update
1: Request
update lock
RY[n] + 54
to 5F
System reserved - Unusable
RY[n] + 60
to 69
(Not used) - - -
RY[n] + 6F (Not used) - - -
RY[n] + 70
to 79
Request to rewrite
instantaneous fl ow
rate setting-1 (P1)
ID 01 to ID 10
*3
Used when rewriting a setting value.
This is input when requesting to rewrite the
instantaneous fl ow rate setting value 1 (P1) of
each sensor amplifi er.
The request input is received by assigning each
sensor amplifi er (ID 01 to ID 10) to each RY.
0->1: Request to
rewrite
RY[n] + 7F
Clear
instantaneous fl ow
rate setting-1 (P1)
rewrite error
*3
Used when rewriting a setting value.
This is input when clearing an instantaneous
ow rate setting-1 (P1) rewrite error.
0->1: Clear error
RY[n] + 80
to 89
Request to rewrite
instantaneous fl ow
rate setting-2 (P2)
ID 01 to ID 10
*3
Used when rewriting a setting value.
This is input when requesting to rewrite the
instantaneous fl ow rate setting value 2 (P2) of
each sensor amplifi er.
The request input is received by assigning each
sensor amplifi er (ID 01 to ID 10) to each RY.
0->1: Request to
rewrite
RY[n] + 8F
Clear
instantaneous fl ow
rate setting-2 (P2)
rewrite error
*3
Used when rewriting a setting value.
This is input when clearing an instantaneous
ow rate setting-2 (P2) rewrite error.
0->1: Clear error
RY[n] + 90
to 99
Request to rewrite
temperature upper
limit setting ID 01
to ID 10
*3
Used when rewriting a setting value.
This is input when requesting to rewrite the
temperature upper limit setting value of each
sensor amplifi er.
The request input is received by assigning each
sensor amplifi er (ID 01 to ID 10) to each RY.
0->1: Request to
rewrite
RY[n] + 9F
Clear temperature
upper limit setting
rewrite error
*3
Used when rewriting a setting value.
This is input when clearing a temperature
upper limit setting-value rewrite error.
0->1: Clear error
RY[n] + A0
to A9
Request to rewrite
temperature lower
limit settingID 01
to ID 10
*3
Used when rewriting a setting value.
This is input when requesting to rewrite the
temperature lower limit setting value of each
sensor amplifi er.
The request input is received by assigning each
sensor amplifi er (ID 01 to ID 10) to each RY.
0->1: Request to
rewrite
RY[n] + AF
Clear temperature
lower limit setting
rewrite error
*3
Used when rewriting a setting value.
This is input when clearing a temperature
lower limit setting-value rewrite error.
0->1: Clear error
RY[n] + B0
to B9
Request to rewrite
integrated fl ow
quantity setting-1
ID 01 to ID 10
*3
Used when rewriting a setting value.
This is input when requesting to rewrite the
integrated fl ow quantity setting value 1 of
each sensor amplifi er.
The request input is received by assigning each
sensor amplifi er (ID 01 to ID 10) to each RY.
0->1: Request to
rewrite
RY[n] + BF
Clear integrated
ow quantity
setting-1 re
write
error
*3
Used when rewriting a setting value.
This is input when clearing an integrated fl ow
quantity setting-1 rewrite error.
0->1: Clear error
RY[n] + C0
to EF
System reserved - Unusable