3-3 Communication Methods
3-23
3
Communicating with the FD-MH series
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-MH) -
Writing settings or status
(1) To see that the sensor amplifier is ready to send/receive commands, check that the "sensor ready"
parameter is set to 1.
(2) Write the data category and command number in the remote register.
Data category: In the high byte, write the data category of the parameter to be written, by referring
to "Command Parameter List" (page 3-24).
Data number: For writing, write 01h in the low byte.
(3) Write the data number in the r
emote register.
Data number: Write the data number of the parameter to be written, by referring to "Command
Parameter List" (page 3-24).
ID number: For data category 00/10, write the ID number of the sensor amplifier, to which the param-
eter is written, in the high byte.
(4) In the remote register, write the data to be written. For details of writable ranges, see "Command
Parameter List" (p
age 3-24).
(5) Execute the command by activating the "request for command" (0 -> 1).
(6) After the command execution completes, the "command completed" signal flips from 0 to 1.
(7) If an error occurs during command execution, the "command error" signal flips from 0 to 1. For
details of the error, check the values entered in the "command response".
(8) Details of the command execution result are stored. For details of the result, see "Command
respons
e list" (page 3-8).
(9) When the "request for command" is set to 0, the "command completed" and "command error"
parameters flip to 0.
PLC
Sensor amplifier
(2)
Data category/command number 0001h (Write command)
RWw00
(3)
Data number 0141h
RWw01
(4)
Data to write             1234h
RWw02
(1)
Sensor ready
RX50
(5)
Command request
RY51
(6)
Command finish
RX51
(7)
Command error
RX52
(8)
Command response 0000h (Successfully completed)
RWr01
Parameter
1
1
1
1
0
0
0
0
(9)
1234h
h
Command number (Write command=01h)
Data category
1 0
h
Data number of parameter to write
ID number of target sensor amplifier
nn
h
Data number of parameter to write
For data category
01/03/05
For data category
00/10