- PROFINET Communication Unit DL-PN1 User's Manual (IB) -
64 Group2 Entry count DINT R 12
65 HIGH setting value (BANK 0) *7 DINT R/W +20.00 -999.99 to +999.99
66 LOW setting value (BANK 0) *7 DINT R/W +10.00 -999.99 to +999.99
67 Shift target value (BANK 0) *7 DINT R/W 0.00 -999.99 to +999.99
68 HIGH setting value (BANK 1) *7 DINT R/W +20.00 -999.99 to +999.99
69 LOW setting value (BANK 1) *7 DINT R/W +10.00 -999.99 to +999.99
70 Shift target value (BANK 1) *7 DINT R/W 0.00 -999.99 to +999.99
71 HIGH setting value (BANK 2) *7 DINT R/W +20.00 -999.99 to +999.99
72 LOW setting value (BANK 2) *7 DINT R/W +10.00 -999.99 to +999.99
73 Shift target value (BANK 2) *7 DINT R/W 0.00 -999.99 to +999.99
74 HIGH setting value (BANK 3) *7 DINT R/W +20.00 -999.99 to +999.99
75 LOW setting value (BANK 3) *7 DINT R/W +10.00 -999.99 to +999.99
76 Shift target value (BANK 3) *7 DINT R/W 0.00 -999.99 to +999.99
77 to 95 Reserved for system
96 Group3 Entry Count DINT R 20
97 Key lock setting DINT R/W 0
0: Release
1: Key lock
98 Bank setting *14 DINT R/W 0
0: Switched to bank 0
1: Switched to bank 1
2: Switched to bank 2
3: Switched to bank 3
99 Timing input *15 DINT R/W 0
0: Timing input OFF
1: Timing input ON
100 Laser emission stop input *15 DINT R/W 0
0: Emission stop input OFF
1: Emission stop input ON
101 to
103
Reserved for system
104 Sub display's screen DINT R/W 0
0: R.V. value screen
1: Analog value screen
2: HIGH setting value screen
3: LOW setting value screen
4: Shift target value setting
screen
105 System parameter *12 DINT R/W 0
Main unit: 0 to 9
Expansion unit: 0 to 1
106 Tolerance tuning setting width *16 DINT R/W 10.00 0.00 to 999.99
107 Calibration function DINT R/W 0
0: No correction (Default)
1: Measured correction
2: Logical correction
108
Measured/Logical correction
target 1
*7 DINT R/W 0.00 -999.99 to +999.99
109
Measured/Logical correction
target 2
*7 DINT R/W +100.00 -999.99 to +999.99
110 to
114
Reserved for system
115
Logical correction measured 1
*7 DINT R/W 0.00 -999.99 to +999.99
116
Logical correction measured 2
*7 DINT R/W +100.00 -999.99 to +999.99
117 to
127
Reserved for system
128 Group4 Entry count DINT R 30
129 Reserved for system
Index
(DEC)
Function name
Description
Data
type
Attribute
Default
value
Value
Page view 18