3-4 Command Parameter List
3-29
3
Communicating with the FD-MH series
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-MH) -
00
nn83 System reserved
nn84 Response time R/W - 3
0: 0.05 s
1: 0.1 s
2: 0.5 s
3: 1.0 s
4: 2.5 s
5: 5.0 s
6: 10.0 s
7: 30.0 s
8: 60.0 s
nn85 Average display *11 R/W - 1.0 00.0 to 10.0 (in steps of 0.5)
nn86
Time-out time for
output 2
R/W - 10 1 to 99
nn87
Integration
direction
R/W - 0
0: Increment
1: Decrement
nn88
Integrated flow
quantity unit
R/W - 2
nn89 to
nn8C
System reserved
nn8D N.O/N.C R/W - 0
Bit 0: Output 1 (1: N.C.)
Bit 1: Output 2 (1: N.C.)
Bit 2: Output 3 (1: N.C.)
nn8E Display mode R/W
FD-MH10A 0
0: Std
1: rESo
FD-MH50A 1
FD-MH100A 1
FD-MH500A 0
nn8F Hysteresis *7 R/W
FD-MH10A 0.10
0.00 to 9.99 *
3
FD-MH50A 00.5
00.0 to 49.9 *
3
FD-MH100A 01.0
00.0 to 99.9 *
3
FD-MH500A 005.0
000.0 to 499.9 *
3
nn90
Bank switching
function
R/W -
1
0: OFF
1: ON
nn91 System reserved
nn92
Flow rate zero
function
R/W - 0
0: OFF
1: ON
nn93 System reserved
nn94 Frequency mode R/W - 0
0: Standard
1: Frequency mode
nn95 to
nn96
System reserved
nn97 Power save mode R/W - 0
0: Do not use
1: Use
nn98 to
nn9C
System reserved
nn9D
Flow indicator
color
R/W - 1
0: Red for ON, green for OFF
1: Green for ON, red for OFF
Data
category
(HEX)
Data
number
(HEX)
Name
Description Attribute Sensor head
Default
value
Parameter range
Data
FD-
MH10A
FD-
MH50A
FD-
MH100A
FD-
MH500A
0 0.01
Cannot
be set.
Cannot
be set.
Cannot
be set.
1 0.1 0.1 0.1
Cannot
be set.
2 1 1 1 1
3 10 10 10 10
4 100 100 100 100
5
Cannot
be set.
1000 1000 1000
6
Cannot
be set.
Cannot
be set.
Cannot
be set.
10000