4-4 Examples of Wiring
4-6
Wiring
SL-V-M-NO4-E
Manual reset mode
When using a simple function type cable (NPN output type cable)
• The shielding wire of the NPN output type cable is connected to +24 V line in the SL-V.
Do not connect the shielding wire to 0 V line.
• If there are some open wiring (completely disconnected), Insulation on those wire are
needed individually.
Automatic reset mode
When using OSSD only
K3
M
IN
OUT
PLC
K1
K2
S1 S2
K2K1
Cable insulation: Black
Cable insulation: Grey
Transmitter
Receiver
(Interlock-reset-ready output) Green
(+24 V) Brown
(+24 V) Brown
(OSSD2) White
(OSSD1) Black
(Reset input) Yellow
(EDM input) Red
(Wait input) Violet
(AUX output) Red
(0 V) Blue
(0 V) Blue
Shield
Shield
K2
K1
(Interlock mode selection input) Pink
Orange/black
(Communication cable 2)
Orange
(Communication cable 1)
K1, K2 : External device (Safety relay, magnet contactor,
etc.)
K3 : Solid state contactor
*1
S1 : The switch for wait input (N.O.)
*1
The violet wire needs to be capped it is not used.
(Open circuit : completely disconnected)
S2 : The switch for reset input (N.O.)
M : 3-phase motor
PLC : For the monitoring use
*1
*1 These are NON SAFETY-RELATED system.
K1, K2 :
External device (Safety relay unit, etc.)
Cable insulation: Black
Cable insulation: Grey
Transmitter
Receiver
(Interlock-reset-ready output) Green
(+24 V) Brown
(+24 V) Brown
(OSSD2) White
(OSSD1) Black
(Reset input) Yellow
(EDM input) Red
(Wait input) Violet
(AUX output) Red
(0 V) Blue
(0 V) Blue
Shield
Shield
K2
K1
(Interlock mode selection input) Pink
Orange/black
(Communication cable 2)
Orange
(Communication cable 1)