- IV Series Users Manual (Field Network) -
Cyclic communication setting method
There are many types of connections, and the connection available for each device are dened in the EDS
le.
The following shows the list of connections that are available in the IV series.
No Connection name Application type I/O
Assembly
Instance
Size
(bytes)
RPI
1
Monitor Data And
External Input
(Monitor/External
input)
Exclusive Owner
This unit
→ Scanner
64H (100) 2 to 392
5 to 10000ms
Scanner
→ This unit
65H (101) 2 to 12
2
Monitor Data (Input
Only)
(Monitor data)
Input Only
This unit
→ Scanner
64H (100) 2 to 392
5 to 10000ms
Scanner
→ This unit
FEH (254) 0
When using the Keyence KV series (EtherNet/IP communication scanner), the names of the connections
with the IV series will be “Monitor/External Input” and “Monitor Data”. The relationship of each connection
name is as described below.
1 : Monitor Data And External Input → Monitor/External input
2 : Monitor Data (Input Only) → Monitor data
The trigger timings of each connection are controlled by the cyclic communications; and both the point-
to-point and Multicast connection types are supported.
If you wish to open “Exclusive Owner” and “Input Only” connections simultaneously, set the connection
type to “Multicast” and match the RPI and the size.
The details of each application type are as described below.
[Exclusive Owner]
This connection allows you to congure the data transmission from the scanner to the IV series, and
vice versa.
This connection type is used when the scanner will not only monitor the data of the IV series but also
provide external input to the IV series.
It is not possible for multiple scanners to open "Exclusive Owner" connections for a single IV series
unit.
[Input Only]
This connection only allows you to congure the data transmission from the IV series to the scanner.
This connection is used when the scanner will only monitor the data of the IV series.
Multiple scanners can simultaneously open “Input Only” connections for a single IV series unit.
If connections will be opened simultaneously from multiple scanners, set the connection type to
“Multicast” and match the RPI and the size.
3
Cyclic communication